UPS Models

Eaton FERRUPS, Service, Battery & Migration Canada

The Eaton FERRUPS (Ferroresonant UPS) is a legacy industrial-grade UPS using ferroresonant transformer technology for extreme load tolerance. The FE series (500 VA to 18 kVA) reaches end of support life in 2027. The FX series is already retired. Deployed in Canadian industrial, oil & gas, mining, and broadcast facilities where load harmonics and power quality challenges make conventional UPS unreliable. We provide battery replacement, transformer service, and migration planning.

3 to 5 yrtypical battery service life
25 Crated battery ambient
24/7emergency line

What a battery test actually measures

BATTERY STRING, IMPEDANCE READINGSOne weak block pulls down the whole string, so every block is measured and trended.12 Vblock 1OK12 Vblock 2OK12 Vblock 3OK12 Vblock 4OK12 Vblock 5OK12 Vblock 6HIGH12 Vblock 7OK12 Vblock 8OKBlock 6 reads high: replace the set, not the single block.

Impedance is read on every block and trended against the baseline. One weak block limits the whole string, which is why sets are replaced together.

UPS Service Canada is not affiliated with Eaton Corporation®

Technical Specifications

Eaton FERRUPS, Ferroresonant Industrial UPS

Output capacity
500 VA to 18 kVA
Topology
Ferroresonant (transformer-based)
Key advantage
Extreme load tolerance, handles non-linear, high-crest-factor loads
Input voltage
120V or 208V (model-dependent)
Output voltage
120V or 208V
Isolation
Full galvanic isolation via ferroresonant transformer
Battery
Internal VRLA + optional extended battery cabinets
FE series
EOSL 2027
FX series
Retired, no OEM support
Replaced by
Eaton 9PX (standard loads) or specialized industrial UPS

Migration Paths

Replacing the FERRUPS post-2027

FERRUPS loads are often non-linear with high crest factors. Not all conventional UPS platforms handle these loads well. We analyse your specific load profile before recommending a replacement to ensure compatibility.

Migration Options

Where FERRUPS users move next

Eaton 9PX

Capacity: 700 VA to 11 kVA

View Eaton 9PX →

Eaton 9SX

Capacity: 700 VA to 11 kVA

View Eaton 9SX →

Eaton 93PM

Capacity: 15 to 200+ kW

View Eaton 93PM →

Request a Quote

FERRUPS, service, battery, or migration assessment

Email us your details, we quote units, batteries, installation, and service contracts. Quote back within 4 business hours.

Include in your email:

  • What you need: Battery replacement / Transformer / capacitor inspection / Migration assessment (post-2027) / Preventive maintenance contract
  • Model (or serial number for battery matching)
  • Quantity and delivery postal code
  • Unit age? Industry (oil/gas, mining, broadcast)? Load type? Battery history? Any alarms or output issues?

FAQ

Eaton FERRUPS questions

What makes FERRUPS different from a conventional UPS?
FERRUPS uses a ferroresonant transformer instead of conventional double-conversion electronics. This provides inherent voltage regulation, full galvanic isolation, and exceptional tolerance for non-linear, high-crest-factor loads. Industrial equipment like variable frequency drives (VFDs), welders, and broadcast transmitters can damage conventional UPS but the FERRUPS handles them without issue. The trade-off is lower efficiency and higher heat output.
What happens when FERRUPS reaches EOSL in 2027?
After EOSL, Eaton will no longer provide OEM parts or service. We will continue servicing FERRUPS units through independent parts channels, but control boards and proprietary components will become increasingly scarce. Battery replacement will remain feasible for years beyond EOSL. For units in critical applications, we recommend beginning migration planning now, replacement projects for industrial UPS typically take 6 to 12 months to specify, procure, and install.
Can I replace FERRUPS with a standard 9PX?
It depends on your load. If your load is standard IT equipment (servers, networking), a 9PX is a straightforward replacement. If your load has high crest factors, significant harmonics, or non-linear characteristics (VFDs, compressors, broadcast), a standard online UPS may not perform well. We analyse your specific load profile with harmonic measurements before recommending a replacement platform.
How often should FERRUPS batteries be replaced?
Same as any VRLA-based UPS: 3 to 5 years depending on temperature and discharge frequency. The ferroresonant transformer itself can last 15 to 20+ years with proper thermal management. The resonance capacitor bank should be tested every 5 years and replaced if degradation is detected.
Do you service FERRUPS in oil & gas and mining facilities?
Yes. FERRUPS is particularly common in Canadian oil & gas (Alberta, Saskatchewan), mining operations, and broadcast facilities. We service these installations across Western Canada with priority dispatch. For remote sites, we coordinate travel and parts staging to minimize on-site time.

Check where your batteries stand